What the calculator models
The calculator estimates total-pressure loss in one rigid, constant-section duct carrying a steady actual volume flow. It combines two parts:
- Distributed friction along the straight length, from the Darcy–Weisbach equation.
- Local fitting losses, from a single summed dimensionless loss coefficient (Advanced mode only).
It deliberately does not try to be a full duct-system design program. It does not solve branching networks, select fans, evaluate noise, or check compliance with any code. It handles one run, at one airflow, in one cross-section. If the flow or the cross-section changes along your path, calculate each section separately and add the compatible losses yourself.
Using the air duct pressure drop calculator in Simple and Advanced mode
Simple mode is the default. You enter shape, airflow, internal dimensions and straight length. The tool fixes the remaining assumptions at illustrative values:
- absolute roughness 0.15 mm,
- air density 1.2 kg/m³,
- dynamic viscosity 18.1 µPa·s,
- no fitting allowance ().
It shows total pressure loss, straight-duct friction rate and air velocity.
Advanced mode keeps those controls and adds editable roughness, density, dynamic viscosity and summed fitting . It also reveals the straight/fitting split, Darcy friction factor, Reynolds number and hydraulic diameter. Switching back to Simple ignores any Advanced property values and fitting allowance and uses the fixed assumptions instead, so the earlier Advanced result is not preserved.
Inputs and units
Units are fixed; there is no imperial option. Numeric fields accept decimals and scientific notation, and out-of-range, blank, malformed or negative entries are rejected.
| Input | Unit | Accepted range | Default |
|---|---|---|---|
| Actual airflow | L/s | 1–50000 | 500 |
| Internal diameter (round) or width (rectangular) | mm | 50–3000 | 400 |
| Internal height (rectangular only) | mm | 50–3000 | 250 |
| Straight duct length | m | 0–1000 | 20 |
| Absolute roughness (Advanced) | mm | 0–3 | 0.15 |
| Air density (Advanced) | kg/m³ | 0.5–2 | 1.2 |
| Dynamic viscosity (Advanced) | µPa·s | 10–30 | 18.1 |
| Summed fitting coefficients (Advanced) | , dimensionless | 0–100 | 0 |
Sliders cover narrower ranges than the typed fields, so you can type a value beyond a slider's end as long as it is inside the accepted range and passes the model limits described later. Inactive controls are ignored: height does nothing for a round duct, and the four Advanced inputs do nothing in Simple mode.
Three input points deserve care:
- Use clear internal dimensions. Nominal or outside dimensions overstate the flow area and understate velocity.
- Enter actual volume flow at duct conditions. The tool does not convert standard-air, free-air, SCFM or compressor FAD figures.
- Enter viscosity as dynamic viscosity, not kinematic viscosity, and keep density and viscosity consistent with the same actual air conditions.
Handy volume conversions (these change units only; they do not convert standard flow to actual flow):
- m³/h to L/s: divide by 3.6
- actual CFM to L/s: multiply by about 0.471947
The pressure loss calculation, step by step
Geometry and velocity
For a round duct of internal diameter , the area is and the hydraulic diameter is . For a rectangular duct with internal sides and :
With actual flow in m³/s, the mean velocity and velocity pressure are:
Velocity pressure is the natural scale for both friction and fitting losses.
Reynolds number
Here is dynamic viscosity in Pa·s (the calculator's µPa·s input multiplied by ). Reynolds number compares inertial and viscous effects and decides which friction regime applies.
Friction factor from Colebrook
The Darcy friction factor (not the Fanning factor, which is one quarter as large) satisfies the Colebrook relation:
where is absolute roughness. Because appears on both sides, it cannot be isolated algebraically. The calculator rewrites the equation as a residual,
and finds the root by 90 bisection steps starting from the interval 0.005 to 0.2, taking the midpoint at the end. It does not substitute an explicit approximation or a fixed friction factor. Solver precision is a numerical property only; it says nothing about how closely a real installation will match.
Losses
The straight-duct friction rate and loss are:
Fittings add:
and the total is:
Two interpretation notes follow from these definitions. The displayed friction rate excludes fittings, so dividing the total loss by length will not reproduce it when . And any you enter must refer to the velocity in the modeled duct section; the tool does not convert coefficients between reference sections.
Worked example: a round run with no fittings
Take the default case: 500 L/s through a 400 mm round duct, 20 m long, with the Simple-mode assumptions. Using unrounded intermediate values:
| Quantity | Value |
|---|---|
| Area | |
| Velocity | |
| Velocity pressure | |
| Reynolds number | |
| Relative roughness | |
| Darcy factor | |
| Friction rate | |
| Straight loss, also the total |
The displayed results round to three significant digits: total loss 9.33 Pa, friction rate 0.467 Pa/m, velocity 3.98 m/s. In Advanced mode the Reynolds number would show as 106000 and the Darcy factor as 0.0196.
You can sanity-check the friction factor by substituting it back into Colebrook. With , the bracket is about , and of that is about 7.134, which matches .
If you add one fitting-like allowance of at this velocity, the fitting loss is Pa, and the total becomes about Pa. A fitting allowance of that size doubles the result, which shows why fittings can matter as much as straight length in short runs.
Worked example: a rectangular duct with a fitting allowance
Now take the same 500 L/s in a 400 mm × 250 mm rectangular duct, 20 m long, with 0.15 mm roughness, 1.2 kg/m³, 18.1 µPa·s and an illustrative .
- Area: , so .
- Hydraulic diameter: (308 mm).
- Velocity pressure: .
- Reynolds number: about 102,000.
- Darcy factor: about 0.0202, giving a friction rate of about 0.986 Pa/m.
- Straight loss: about 19.7 Pa.
- Fitting loss: .
- Total: about 49.7 Pa.
Notice that the fitting allowance, not the 20 m of straight duct, supplies most of the total here. The value is only illustrative; it is not a standard coefficient for any specific elbow, damper or installation. Use a manufacturer's or other documented coefficient, referenced to this duct's velocity.
The rectangular case also shows why the tool states its approximation openly. It uses the true area for velocity and hydraulic diameter for friction. Hydraulic diameter is not the diameter of a round duct that gives equal friction at equal flow, so do not read "308 mm" as an equivalent round size.
How the result responds to changes
Understanding scaling helps you read results without recalculating every time.
- Length. With flow, geometry, properties and unchanged, straight loss is proportional to length. Doubling the default run to 40 m doubles the straight loss to about 18.7 Pa. Fitting loss does not depend on length, so a zero-length run with nonzero gives a fitting-only result.
- Airflow. Velocity pressure is proportional to , so with fixed, fitting loss scales exactly with . Doubling the rectangular example's flow to 1000 L/s gives m/s, Pa and a fitting loss of 120 Pa, four times 30 Pa. Straight loss rises a little less steeply than the square in the turbulent range, because tends to fall as Reynolds number rises. Avoid assuming an exact square law for friction.
- Size. For a round duct at fixed flow, , and the friction rate would scale roughly as if were constant. In practice also shifts with , but the message holds: modest changes in diameter produce large changes in friction rate.
- Roughness. Raising increases , and its effect grows with Reynolds number as the flow becomes more roughness-dominated.
Model boundaries and rejected inputs
Passing the input ranges is not enough. The calculator also rejects any result outside these coupled limits (equality is allowed):
| Condition | Rejected when |
|---|---|
| Reynolds number | |
| Velocity | m/s |
| Relative roughness | |
| Total modeled loss | Pa |
| Rectangular aspect ratio |
Some practical consequences:
- 500 L/s through a 100 mm round duct would need m/s, so it is rejected.
- A 800 mm × 200 mm duct is accepted at an aspect ratio of exactly 4, but 1000 mm × 200 mm is not.
- Very low flow in a large duct can fall below . The tool returns no laminar or transitional estimate and does not fall back on .
When any active input is invalid or a limit is hit, results show an em dash, an error banner and a control-level message appear, Copy and Print/PDF are disabled, and the chart is replaced by a correction message.
These limits belong to this calculator. They are not HVAC design targets, noise criteria or regulatory thresholds, and they do not guarantee that air compressibility is negligible for every application.
Reading the results and the graphic
The chart plots cumulative total-pressure loss against the entered straight length. An orange slope represents friction along the run, and a blue vertical step at the end represents summed fitting losses. Fittings are grouped at the end purely for illustration; the graphic is not a measured static-pressure profile and does not place individual fittings. Zooming, panning and Reset Viewport change only the view, not the calculation.
Results are rounded to three significant digits, with unnecessary trailing zeros removed, so a value may appear as "5 m/s" rather than "5.00 m/s". Those digits describe arithmetic, not measurement certainty: uncertainty in roughness, fitting coefficients, dimensions and installation quality is usually far larger than the rounding.
Copy produces a summary of active inputs, visible results, assumptions and advisories. Print/PDF opens the browser print dialog after expanding collapsed panels. Reset restores the default Simple round case. Presets load their own modes and values. CSV download and shareable state URLs are not available.
What the result means and what it leaves out
For a horizontal constant-area run at unchanged density, velocity pressure stays constant along the duct, so the modeled total-pressure loss equals the static-pressure drop. In other situations, such as changes in area or elevation, static and total pressure do not move together, and this tool does not model those effects.
The result is a loss for the run you entered. It is not a fan external-static-pressure rating and does not include:
- filters, coils, terminals or other equipment (these need separate allowances),
- other duct sections or branches,
- static regain, elevation, leakage or balancing,
- fan system effects.
Flexible, corrugated, compressed or internally lined duct needs applicable manufacturer data; changing the roughness value alone does not capture how those products behave once installed. The 0.15 mm default is an illustrative galvanized-steel assumption, not a construction specification. In Advanced mode, density and viscosity are values you supply; the tool does not derive them from temperature, pressure, altitude or humidity. For critical sizing, especially with rectangular ducts, check against appropriate manufacturer data.
Frequently asked questions
Is the answer the pressure my fan needs to deliver?
Not by itself. It is the modeled loss in one duct run. A fan selection must account for every component in the airflow path, the system layout, and the fan's installed conditions.
Why does the friction rate differ from total loss divided by length?
The friction rate describes only the straight duct, . Total loss includes , which does not scale with length, so whenever .
Can I enter airflow in CFM or m³/h?
Convert to L/s first (m³/h ÷ 3.6; actual CFM × about 0.471947). These conversions apply only to actual volume flow at duct conditions. Standard or free-air flow must be converted to actual flow separately before entry.
How do I handle several fittings?
Add their loss coefficients into one , provided every coefficient refers to the velocity in the modeled duct section. Coefficients referenced to another section must be converted outside the tool.
What if my duct changes size partway along?
Run each constant-section segment separately, with its own dimensions and compatible fittings, and sum the losses along the same flow path. The calculator does not allocate flow between branches.
Why was my input rejected even though each field is in range?
The coupled limits on Reynolds number, velocity, relative roughness, aspect ratio and total loss also apply. The error message identifies the control to correct.
Read the formula definitions, supported input ranges, and limitations before using this estimate.